What sets the Helios apart from other Large Display Meters is its dual line display with super bright LEDs that can be read even in bright sunlight. The dual line display simplifies programming and also makes it possible to display more information. For instance, the upper line can display the process variable and the lower line a tag or a different scale of the input. In a flow application, one line could display flow rate and the other line flow total. Even if you are not installing the Helios outdoors in bright sunlight, you will appreciate its big, clear, bright display that can be seen from up to distances of 100 feet (30 meters).

Go with the Helios PD2-6080 when you have multiple, (up to 16), Modbus registers you want to display on a single large display meter. The PD2-6080 can also accept two 4-20 mA signals. The PD2-6080 can be programmed as a Modbus RTU Master, Slave or Snooper allowing it to work in just about any Modbus application. Typically, the upper line displays the PV and the lower line displays the tag.

Input
 

Modbus® RTU; Two (2) 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V


 

Helios Features

• Large 1.80" Digits
• Dual Line Display
• Six Full Digits on Each Line
• Readable From 100 Feet Away
• Superluminous Sunlight Readable Display
• IP65 Rated Field Mountable Enclosure
• Great for Outdoor Use: -40 to 150°F (-40 to 65°C)
• Program the Meter from a PC with Onboard USB and ScanView

PD2-6080 Features


• Modbus® RTU Master, Slave, or Snooper Mode
• Poll and Display up to 16 Process Variables
• Math Functions Capabilities
• Isolated 24 VDC @ 200 mA Transmitter Power Supply
• Multi-Pump Alternation Control
• Signal Input Conditioning for Flow & Round Horizontal Tank
• Programmable Displays & Function Keys
• 32-Point, Square Root, or Exponential Linearization
• Up to Three 4-20 mA Analog Outputs Available
• Current Input Protected by Resettable Fuse

Input/OutputModbus RTU over RS-485, Two analog inputs (4-20 mA, ±10 V)
DisplayTwo lines with 1.8" (46 mm) high digits, red LEDs; 6 digits per line (-99999 to 999999), with lead zero blanking
Display IntensityEight user selectable intensity levels
Display Update Rate5/second (200 ms)
Over RangeDisplay flashes 999999
Under RangeDisplay flashes -99999
Programming MethodsFour programming buttons, digital inputs, PC and ScanView software, or Modbus registers.
Max/Min DisplayMax/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
PasswordThree programmable passwords restrict modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs.
Power Options85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ± 10%, 15 W max. Powered over USB for configuration only.
Isolated Transmitter Power SupplyTerminals P+ & P-: 24 VDC ± 10%. 12-24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal P+/P- switch). 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
Non-Volatile MemoryAll programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
FuseRequired external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Isolation4 kV input/output-to-power line; 500 V input-to-output or output-to-P+ supply
Overvoltage CategoryInstallation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
EnvironmentalOperating temperature range: -40 to 150°F (-40 to 65°C); Storage temperature range: -40 to 185°F (-40 to 85°C); Relative humidity: 0 to 90% non-condensing
ConnectionsRemovable and integrated screw terminal blocks accept 12 to 22 AWG wire.
EnclosureUL Type 4X, IP65 rated. Polycarbonate & glass blended plastic case, color: gray. Includes four PG11 through-hole conduit openings, with two factory installed PG11, IP68, black nylon threaded hole plugs with backing nuts.
Wall MountingFour (4) mounting holes provided for mounting meter to wall.
Pipe MountingOptional pipe mounting kit (PDA6260) allows for pipe mounting. Sold separately.
See PD2-6080/81 manual for instructions.
Tightening TorqueRemovable Screw Terminals: 5 lb-in (0.56 Nm)
Digital I/O and RS485 Terminals2.2 lb-in (0.25 Nm)
Overall Dimensions (H x W x D)10.63" x 12.59" x 4.77" (270 mm x 319.7 mm x 121.2 mm)
Weight6.10 lbs (2.76 kg)
UL File NumberUL & C-UL Listed. E160849; 508 Industrial Control Equipment.
USB ConnectionCompatibility: USB 2.0 Standard, Compliant Connector Type: Micro-B receptacle
Cable: USB A Male to Micro-B Cable
Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
Power: USB Port
Warranty3 years parts & labor
  • Thumbnail of document Data Sheet - PD2-6080 Helios Modbus Scanner
    Download

    Data Sheet - PD2-6080 Helios Modbus Scanner

    Download
  • Thumbnail of document Manual - PD2-6080 Helios Modbus Scanner
    Download

    Manual - PD2-6080 Helios Modbus Scanner

    Download
  • Thumbnail of document Software - PD2-6080 Helios Modbus Scanner
    Download

    Software - PD2-6080 Helios Modbus Scanner

    Download

Accessories

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more